Your shopping cart is empty!
Apollo AlarmSense CS heat detector (static temperature) 55000-193
- Brand: Apollo
- Product Code: 55000-193
- Availability: 3-5 Days
£14.27 Inc VAT £11.89 Ex VAT
Static heat detector reacts only when a fixed temperature is reached.
Ideal for use in environments with rapid temperature fluctuations such as boiler rooms etc.
Suitable for use with C-TEC's CFP AlarmSense range of 2-8 Zone Two-Wire Fire Panels.
Housed in a pure white polycarbonate moulding.
Fitted with two alarm LEDs to allow 360º visibility
9-33V DC operating voltage.
Requires a 45681-244 AlarmSense base.
Approvals/certifications Certified to EN54-5 by UL International (UK) Limited.
Application/operation Generates an alarm condition when it detects a temperature of between 84ºC & 100ºC.
Application temperature 55°C typical, 80°C max.
Static response temperature 84°C min, 100°C max.
Supply wiring 2-wire monitored, polarity insensitive.
Supply/operating voltage 9 to 33V DC.
Quiescent current 50µA @ 15 VDC.
Alarm voltage 9-33V DC.
Alarm current 1.5mA @ 2-8.5V; 25 +/- 2mA @ 10.5-15V; 1.5AmA @ 18-24V; 2mA @ 33V.
Alarm reset voltage 2V max (1 second alarm reset time).
Product dimensions (mm) 100mm diameter x 42m deep (detector only); 100mm diameter x 50mm deep (detector in base).
Construction & finish White polycarbonate.
.Weight 100g.